SKU: 7753
Accent Air – Rheem Outdoor LCD PCB
$490.00
The Outdoor Board controls the external refrigeration unit, which includes the reversing valve, compressor and outdoor fan. It also provides sensory feedback of the outdoor coil temperature, which is used by the Indoor Board to control the outdoor fan speed and to manage the de-ice cycle.
The Outdoor Board also has High pressure (HP) and Low Pressure (LP) inputs for protection of the compressor. There are also Manual inputs available for activating the Compressor and Reversing Valve, when the Outdoor unit is used stand-alone with an external thermostat/control.
Out of stock
We Accept
Outdoor Specifications:
- Power supply: 240 VAC 50Hz
- Fuse: 250VAC 3.15A Slow Blow
- Operating conditions: -10º to 50ºC, 5% to 85% RH (non-freezing and non-condensing)
- Compressor, Reversing Valve, Fan Relay Output: Output 240VAC 50Hz, Contact Rating 2A 250VAC, max power 4kVA
- Clean Contact Relay output: Output 240VAC 50Hz, Contact Rating 2A 250VAC, 5A 125 VAC, 3A 30VAC, 5A 30VDC, max power 4kVA
- Fan AC Motor Speed Drive: Max Current 2A 250VAC 50Hz, Peak Surge Current 100A, Full Cycle Modulation
- Coil Temperature Sensor: Thermistor 50K Beta 4050
- Compressor/Reverse Manual Input: 24VAC 50Hz or 240VAC 50Hz input
We use Australia Post for all deliveries, with a tracking number.